Test sequence and
descriptions
The following tests are carried out with the
SUPPLY SWITCHED OFF
1. Extenal earth fault
loop impedance
Reason: To establish that a good earth exists
at the installation in order for the remaining tests to go
ahead.
Method: An earth fault loop impedance tester is
connected at line and earth at the supply side of the
installation and a test performed. The result is Ze and
recorded on the sheet. The prospective fault current is
measured at the same time.
2. Continuity of
protective and bonding conductors
Reason: To check that all circuit protective
conductors (green and yellow cables) are continuous and are
present at every electrical accessory on the circuit. Also to
check that the main earthing conductor and main bonding
conductors are continuous and correctly connected.
Method 1: The line conductor is connected to
the circuit protective conductor of the same circuit at the
consumer unit and a measurement taken at ALL accesories on that
circuit between line and c.p.c. The highest measurement
obtained is recorded on the test report. Test result is R1 +
R2. The line conductor and neutral conductor are then connected
and the above repeated to obtain R1 + Rn
Method 2 (used for main earth and main bonding
conductors):A wandering lead is connected to one
end of the conductor to be tested and a measurement taken
between the other end of this lead and the other end of the
conductor. Test result is R2.
During this test polarity can be checked as
well. The continuity of the neutral conductor can also be
checked.
3. Continuity of ring
final circuit conductors
Reason: This test ensures that all ring final
circuits (sockets usually) are indeed a continuous ring with no
interconnects or breaks within it.
Method: The line, neutral and earth conductors
of the circuit are identified and a measurement from one end to
the other end of each is taken. These results are r1, r2 and
rn. The incoming line conductor is then connected to the
outgoing earth conductor and the outgoing line conductor is
connected to the incoming earth conductor. A measurement is
then taken at ALL socket outlets on the ring. The highest of
which is recorded on the report. This result is R1+R2 for that
circuit. The above is then repeated using the neutral conductor
instead of the earth conductor. This test provides R1+Rn which
does not need to be recorded on the report but is essential to
check the circuit correctly.
4. Insulation
Resisitance
Reason: This test checks whether the insulation
around a cable is still intact and has not broken down over
time. It is a good indicator of the age of an
installation.
Method: An insulation resistance tester is
connected across line and neutral tails at the origin of the
supply. 500V are then pumped down the conductors to see if any
voltage leaks across from one conductor to the other. The same
is then done for the line and earth and the earth and neutral
conductors. In a healthy installation there should be no
voltage leakage.
5. Polarity
Reason: To check that all accesories are
correctly connected to line, neutral and earth and that all
switches and circuit breakers are connected in the line
conductor only.
Method: The method for this is the same as for
continuity and is usually done at the same time by operating
switches etc whilst conducting the test.
6. Earth electrode
resistance
Reason: To make sure that any earth electrode
used is of a sufficiently low impedance to allow the timely
operation of the RCD protecting the installation.
Method: An earth fault loop impedance tester is
connected between line and earth at the origin of the supply
and a test performed. The result of which is considered the
resistance of the electrode (Ra).
The following tests are carried out with the
SUPPLY SWITCHED ON
7. Earth fault loop
impedance
Reason: This test is
done at the furthest point on a circuit in order to make sure
the impedance of the earth path is not too high even at the
furthest point so that sufficient current will flow under fault
conditions to bring out the circuit breaker protecting the
circuit.
Method:
An earth fault loop impedance tester is connected to line and
earth at the furthest point on the circuit and the test
performed.
8. RCD test
Reason: To make sure
RCD's trip within the correct time
Method:
An RCD tester is connected at the furthest point in a circuit
and a test at 1/2 times, 1 times and 5 times the trip current
is performed and a time of trip obtained. Usually
milli-seconds. The test button is then pressed.
9. Functional
testing
Reason:
To make sure all switches, isolators, MCB's etc. work as they
should.
Method.
Self explanatory.
|